Module has a strain relief and terminal cover. Wires are attached via captive screw terminal allowing a maximum cable cross-section of 2.5 mm2. The packaging meets Protection class 2 requirements.
The DALI 3-RM-C is connected to the DALI bus and to the mains supply. The contactor coils must be equipped with an appropriate threshold diode and 24 V signal lamps can be connected directly.
IMPORTANT: DALI is not SELV. The installation instructions for low voltage therefore apply.
Circuit diagram for three contactors with a maximum power of 8 W:

IMPORTANT : The contactors must be equipped with an appropriate threshold diode. Operation without a threshold diode is not permitted. The controller is designed for a maximum load of 25 W. This load can be split among the three channels. The loads may be distributed asymmetrically.
Circuit diagram for one contactor with a maximum power of 25 W:

IMPORTANT: Outputs Ch1 and Ch3 may not be short-circuited. The entire output may flow via one output.
Example of a main circuit:

IMPORTANT: Please check the inrush currents of the switched loads. Electronic control gear may have very high inrush currents. Check with the contactor manufacturer.
| Conformity and Standards |
| Emission |
EN55 015, EN 61000-3-2 |
| Immunity |
EN 61 547 |
| Safety |
EN 61558-2-17 |
|